63 1160 M9182, M9183, M9185, M9186 Modutrol IV Motors

2016-10-06

: Pdf 169798-Attachment 169798-Attachment B5 unilog

Open the PDF directly: View PDF PDF.
Page Count: 4

® U.S. Registered Trademark
Copyright © 1996 Honeywell Inc. • All Rights Reserved
SPECIFICATION DATA
M9182, M9183, M9185, M9186
Modutrol IV™ Motors
APPLICATION
M9182, M9183, M9185 and M9186 are proportioning spring
return motors used to operate dampers and valves.
M9182
M9183
M9185
M9186
FEATURES
Replaces M945A,D,F and M955 Motors.
Rated for 60 lb-in. torque.
Oil immersed motor and gear train for reliable
performance and long life.
Wiring box provides NEMA 3 weather protection.
Quick-connect terminals standard—screw terminal
adapter available.
Adapter bracket for matching shaft height of older
motors is standard with replacement motors.
Integral auxiliary switches are available factory
mounted, or can be field added to TRADELINE®
models.
Field addable interface modules can be mounted in
wiring box to upgrade actuator to Series 70
(electronic) control.
Auxiliary end shaft on TRADELINE® model can
operate valve linkage. For use in normally open valve
applications.
Die-cast aluminum housing.
63-1160-2
2
M9182, M9183, M9185, M9186 MODUTROL IV™ MOTORS
63-1160—2
SPECIFICATIONS
TRADELINE® Models
TRADELINE® models are selected and packaged to provide
ease of stocking, ease of handling, and maximum
replacement value. TRADELINE® model specifications are
the same as those of standard models, unless otherwise
specified. TRADELINE® model is M9185D1004.
TRADELINE® model has auxiliary switch cams.
Standard Models
M9182A,C,D,W
M9183G
M9185A,B,C,D,E
M9186G
Control Type
91 is Series 90
Power Rating
8is high torque: 60 lb-in.
Output Drive
5is spring return
normally closed, dual-
ended shaft
6is spring return
normally open, dual-
ended shaft
2is spring return
normally closed,
single-ended shaft
3is spring return
normally open, single-
ended shaft
Suffix Letter
A: Fixed stroke
(90° or 160°),
No auxiliary switches
B: Fixed stroke
(90° or 160°),
1 auxiliary switch
C: Fixed stroke
(90° or 160°),
2 auxiliary switches
D: Adjustable stroke
(90° to 160°),
No auxiliary switches
E: Adjustable stroke
(90° to 160°),
1 auxiliary switch
G: Fixed stroke
(90° or 160°),
No auxiliary switches,
Electrically normally
open (motor drives
open, clockwise, when
powered and control
wiring not connected)
W:Fixed stroke
(90° or 160°),
1 auxiliary switch
HHHH
Electrical Ratings:
M9182,
M9183,
M9185, M9186 Voltage
(V at 50/60 Hz) Current
Draw (A)
Power
Consumption
(W)
Without
Transformera24 1.0 23
With Internal 120 0.28 28
Transformer 208 0.16 28
240 0.14 28
aInternal transformer can be field added.
Controller Type:
Series 90 Control Circuit: 135 ohm, Series 90 proportioning
controller. Series 90 high or low limit controller with manual
minimum position potentiometer (with a combined total
resistance of up to 500 ohms) can also be used in the control
circuit.
Motor Rotation:
M9182, M9185 Motors spring counterclockwise (as viewed
from power end) to a closed position on power interruption.
M9183, M9186 Motors spring clockwise to an open position
on power interruption.
Stroke:
Fixed Stroke Models: 90° or 160°.
Adjustable Stroke Models: Can be set between 90° and 160°.
Timing:
Nominal 30 seconds for 90° stroke and 60 seconds for
160° stroke.
NOTE: M9182D1023 timing is 2 min. for 90° stroke, or 4 min.
for 160° stroke. It contains on-off pulsing circuitry to
achieve timing. Intermittent operation is normal.
Torque:
60 lb-in. (6.8 N•m).
Maximum Damper Rating:
B dim = 68 in. (1727 mm).
Dead Weight Load on Shaft:
Power or Auxiliary End: 200 lb (90.8 kg) maximum.
Maximum Combined Load: 300 lb (136 kg).
Auxiliary shaft not included on M9182, M9183 Motors.
Ambient Temperature Ratings:
Maximum: 150°F (66°C) at 25% duty cycle.
Minimum: minus 40°F (-40°C)
Crankshaft: 3/8 in. (9.5 mm) Square.
M9185, M9186 have double-ended shafts.
M9182, M9183 have single-ended shafts.
Dimensions:
See Fig. 1.
Underwriters Laboratories Inc. Listed:
File No. E4436, Guide No. XAPX.
Canadian Standards Association Certified:
General Listing File No. LR1620, Guide No. 400-E.
Auxiliary Switch Ratings (Amperes):
One Contacta120V 240V
Full Load 7.2 3.6
Locked Rotor 43.2 21.6
a40 VA pilot duty, 120/240 Vac on opposite contact.
M9182, M9183, M9185, M9186 MODUTROL IV™ MOTORS
363-1160—2
Accessories:
ES650117 Explosion-proof Housing: Encloses motor for
use in explosive atmospheres. Not for use with Q601,
Q618, and Q455 Linkages. Order separately from
Nelson Electric Co. Requires Honeywell 7617DM
Coupling.
Q607 External Auxiliary Switch: Controls auxiliary
equipment as a function of motor position.
Internal Auxiliary Switch Kits: Can be field-installed on
TRADELINE® models.
220736A: One-switch Kit.
220736B: Two-switch Kit.
Q605 Damper Linkage: Connects motor to damper.
Includes motor crank arm.
Q618 Linkage: Connects Modutrol motor to water or
steam valve.
Q601 Bracket and Linkage Assembly: Connects Modutrol
motor to water or steam valve.
Q100A,B Linkage: Connects Modutrol motor to butterfly
valve. Requires adapter bracket packed with motor.
Q209E,F Potentiometer: Limits minimum position of motor.
Q68 Dual Control Potentiometer: Controls 1 to 9
additional motors.
Q181 Auxiliary Potentiometer: Controls 1 or 2 additional
motors.
221455A Infinitely Adjustable Crank Arm: Approximately
0.75 inch (19 mm) shorter than the 4074ELY Crank
Arm. Can rotate through downward position and clear
base of motor without requiring use of adapter bracket.
220741A Screw Terminal Adapter: Converts the standard
quick-connect terminals to screw terminals.
Transformers: Mounted internally, provide 24 Vac power
to motor.
198162JA: 24 Vac; 50/60 Hz (for electrical isolation).
198162EA: 120 Vac; 50/60 Hz.
198162GA: 220 Vac; 50/60 Hz.
198162AA: 120/208/240 Vac; 50/60 Hz.
Q7130A: Interface Module with selectable voltage ranges
(4-7 Vdc, 6-9 Vdc, and 10.5-13.5 Vdc). Adapts motor to
M71XX function.
Q7230A: Interface Module, selectable voltage or current
control, with adjustable null and span. Adapts motor to
M72XX function; 4 to 20 mA or 2 to 10 Vdc.
Q7330A: Interface Module, for W936 Economizer
applications. Adapts motor to M73XX function.
Q7630A: Interface Module, 14-17 Vdc control with
minimum position capability. Adapts motor to M76XX
function.
7617ADW Adjustable Crank Arm: approximately 0.75 in.
(19 mm) shorter than the 7616BR Crank Arm.
4074BYK: Controls up to 6 M91XX motors in unison from
one Series 90 Controller.
4074EAU: Drives 2 or 3 M91XX motors from a W973
Single-zone Logic Panel and W7100 Discharge Air
Controller.
4074EDC: Drives one M91XX motor from a 4-20 mA
controller.
4074EED: Drives up to 4 M91XX motors from a 4-20 mA
controller.
221508A Resistor Board: Plugs onto quick-connects in
wiring box of M91XX motor. Can be used in place of
4074BYK, EAU, EDC, or EED resistor kits (functions
described above).
4
M9182, M9183, M9185, M9186 MODUTROL IV™ MOTORS
63-1160—2
Honeywell Europe S.A.
3 Avenue du Bourget
B-1140 Brussels Belgium
Honeywell Asia Pacific Inc.
Room 3213-3225
Sun Hung Kai Centre
No. 30 Harbour Road
Wanchai
Hong Kong
Home and Building Control
Honeywell Limited-Honeywell Limitée
155 Gordon Baker Road
North York, Ontario
M2H 2C9
Honeywell Latin American Division
Miami Lakes Headquarters
14505 Commerce Way Suite 500
Miami Lakes FL 33016
Helping You Control Your World
63-1160—2 G.R. Rev. 5-96
Home and Building Control
Honeywell Inc.
Honeywell Plaza
P.O. Box 524
Minneapolis MN 55408-0524
Printed in U.S.A. on recycled paper
containing at least 10% post-consumer paper fibers
1-1/4
(32)
2-1/2 (64)
1-3/4
(44)
5/32
(4)
4-7/8
(124)
5-1/2
(140)
25/32
(20)
4-1/16 (103)
1/2
(13)
31/32
(24)
1/4
(7)
1-15/32
(37)
WIRING
BOX
BASE
MOTOR
AUXILARY
END
POWER
END
ADAPTER
BRACKET
3/4 (19)
2-19/32
(66)
5-13/32
(137)
6-15/32
(164)
1-1/2 (38) 3-29/32 (98)
19/32 (15)
8-3/4 (223)
3/4
(19)
TOP VIEW OF BRACKET ONLY
3-15/16
(100)
4-7/32
(107)
2-5/16
[58]
5/8
(16)
25/32
(20)
4-7/8 (124)
7/16
(11)
5-3/8 (136)
1/4 (7)
5-13/16
(148)
POWER END
M366E
Fig. 1. Dimensions of M9185 and M9186 in in. (mm).
NOTE: M9182, M9183 do not have auxiliary shafts. All other dimensions are the same.